WEIGHT CONTROLLER - MASAM
Weight controllers “mASAm” are designed to measure the weight of liquid and bulk materials and display the data on the operator panel. In-house production and know-how of the leading engineers of the company allowed to create a quality weight controller, the price of which is much lower than that of similar products available on the market. Reliability and quality of the weight controller “mASAm” is proven by successful use of this equipment in processes of production of explosive substances, where the importance of dosage of components is, without exaggeration, of vital importance.
Technical Specifications
Name of characteristic / parameter |
Meaning of characteristic |
||||
mASAm-01 | mASAm-01Ex | mASAm-02Ex | MiSs-4С | MiSs-4CEx | |
Power supply from an external voltage source: | |||||
– rated voltage (VDC, V) | 24 | 24 | 24 | 24 | 24 |
– voltage range (VDC) | 10 to 14 (direct)
19.2 to 30 (with IDE) |
10 to 14 (direct)
19.2 to 30 (with IDE) |
10 to 14 (direct)
19.2 to 30 (with IDE) |
10 to 14 (direct)
19.2 to 30 (with IDE) |
10 to 14 (direct)
19.2 to 30 (with IDE) |
– amperage consumption (A) | 0,104 | 0,104 | 0,104 | 0,104 | 0,104 |
– weight mode 16 sensors 350 (Om) | 0,32 | 0,1 | 0,1 | 0,32 | 0,32 |
Power consumption (W) | 10 | 3 | 3 | 10 | 3 |
Number of measuring channels | 4 | 4 | 4 | 4 | 4 |
Sensitivity of input signal (μV \ division) | 0,75 | 0,75 | 0,75 | 0,75 | 0,75 |
Maximum value of output signal (mV) | 23 | 23 | 23 | 23 | 23 |
Sensor supply voltage (V) | 5 | 5 | 5 | 5 | 5 |
Sensor type | Strain gauge bridge type | ||||
Measuring channels intrinsic safety assurance | – | Yes | Yes | – | Yes |
Measuring channels intrinsic safety | – | safety barrier in Safe-area | safety barrier in Safe-area | – | safety barrier in Safe-area |
Connection to external ACS | Yes | Yes | Yes | Yes | Yes |
Communication interface | RS-485 | RS-485 | RS-485 | RS-485 | RS-485 |
Communication protocol | Modbus RTU | Modbus RTU | Modbus RTU | Modbus RTU | Modbus RTU |
Built-in digital display | LCD 4 lines of 20 characters | LCD 4 lines of 20 characters | 5 characters seven segment display | No | No |
Measuring range (kg) | Determined by load cell LEL | ||||
Maximum permissible systematic component of basic error Δcr,% | ± 0,1 of nominal value | ||||
Operating conditions: | |||||
– ambient temperature (°С) | from 0 to 40 | from 0 to 40 | from 0 to 40 | from 0 to 40 | from 0 to 40 |
– Relative humidity (non-condensing),% | 30 to 80 | 30 to 80 | 30 to 80 | 30 to 80 | 30 to 80 |
– frequency range of vibration (Hz) | 5 to 35 | 5 to 35 | 5 to 35 | 5 to 35 | 5 to 35 |
– explosion zone class | – | 2, 21, 22 | 1 | – | 2, 21, 22 |
– explosion protection level (НПАОП 40.1-1.32) | – | 1ExeIICT4,
ExiaIICT4 |
1ExeIICT4,
ExiaIICT4 |
– | 1ExeIICT4,
ExiaIICT4 |
Degree of protection of enclosure | IP20 | IP65 | IP67 | IP65 | IP67 |
Overall dimensions (HхWхL), mm | 166х242х50 | 207х257х132 | 160х260х90 | 160х260х90 | 310х210х84 |
Weight, kg (max) | 3,0 | 3,0 | 3,0 | 3,0 | 3,0 |
Functional purpose of weight controllers:
– receive signals from bridge-type strain gauges;
– provide the ability to set zero weight and calibrate sensors by means of buttons;
– provide indication of weight, tare and error measurements by means of digital display;
– can be configured via RS-485 interface;
– provide network communication with other similar devices and APCS;
– provide intrinsic safety of measuring channels and communication channels.
All components and materials of weight controllers are subject to incoming inspection in accordance with GOST-N PMG33 requirements. Only components that passed the incoming inspection with a positive result are allowed in production.
Completion:
mASAm-01 | mASAm-01Ex | mASAm-02Ex | MiSs-4С | MiSs-4CEx |
Плата ASA-ІНЖИНІРИНГ
mASAm ver.1147+ body G232 IP20 |
Плата ASA-ІНЖИНІРИНГ
mASAm ver.1147+ корпус IP65 DC007LGNO Gainta for the zone 2, 21, 22 |
Плата ASA-ІНЖИНІРИНГ MiSs-4С ver.001/0597+body Rose Ex IP67 for the zone 1
|
Плата ASA-ІНЖИНІРИНГ
MiSs-4С ver.001/0597+body IP65 Gainta G2018 |
Плата ASA-ІНЖИНІРИНГ
MiSs-4С ver.001/0597+ body ДИГ КСВ-4-16У1 (II 2G ExeibIIc T5 Gb) for the zone 2, 21, 22 |
The following documentation is included in the delivery set:
– passport for the product;
– operation manual;